Cladding render brickwork

Non-compliant or corroding external fixings and screws

5 examples in 4 videos 4 major 1 minor

What it is

An entire horizontal row of fixing nails was omitted during the installation of the rectified cladding panels before scaffolding began removal.

Non-compliant Class 2 internal bugle screws were used to fasten exterior wall elements beneath the render. Exposure to trapped moisture is causing the screws to heavily rust and blow out the surrounding wall surface.

Lower sheet panels on the front facade were installed poorly with inadequately positioned weep hole trims and non-compliant Class 2 nails. The nails are already visibly corroding and bleeding through the panel finish.

Standards

Explained in our own words. Check the current edition; which edition applies depends on the building permit date.