Valley and Eaves Gutter Clearance and Discharges

4 examples in 4 videos 4 major

What it is

Roof tiles extend excessively across the valley, failing to provide the mandatory clearance width needed for water conveyance. The clearance does not satisfy design rainfall intensity requirements.

The valley gutter clearance measures only 90 mm instead of the mandatory 180 mm required for this high rainfall intensity area. This inadequate width can lead to water overtopping into the roof cavity during heavy rain.

The box gutter expansion joint is non-functional because the channel was never cut to provide a physical thermal break, merely hidden with a cover strip.