Window Flashings and Openings
What it is
Cladding originally fitted tight against window flashings was mechanically ground back on site, scoring and damaging the metal flashings. The cut flashings do not extend 110 mm past openings, leaving them susceptible to corrosion and water ingress.
External cladding lacks head and sill flashings around the window, and finishes tight against the metal roof sheeting without the mandatory 50 mm clearance gap. Furthermore, the parapet capping is not secured and lacks minimum drainage fall.
Wall flashings are poorly executed or completely omitted across cladding sections. Where head flashings are installed, they fail to extend past the window openings by the manufacturer or code required distance.
Standards
- AS 1562.1 Suggested reference, unverified
- AS 4200.2 Suggested reference, unverified
- NCC Suggested reference, unverified
- NCC Vol 2 Suggested reference, unverified
- Weathertex Installation Manual Suggested reference, unverified
Explained in our own words. Check the current edition; which edition applies depends on the building permit date.