Inadequate clearances and plumbing separation requirements
What it is
The external overflow relief gully is set at only 40 mm below internal floor level rather than the required minimum separation of 150 mm, risking internal sewage surcharge.
Gas lines are installed touching or without statutory separation from adjacent water pipes in the roof cavity.
Standards
- AS/NZS 3500 Said in video
- AS/NZS 3500.2 Suggested reference, unverified
- AS/NZS 5601 Said in video
Explained in our own words. Check the current edition; which edition applies depends on the building permit date.
Also relevant to
Video examples
- Unbelievable! Building Surveyor Approved This... 14:15 majorOverflow relief gully height less than 150 mm below lowest fixture
- Unbelievable! Building Surveyor Approved This... 23:18 majorInadequate clearance between gas piping and adjacent water services