Inadequate roof flashing upstand height and fixing spacing
What it is
Roof lead flashings and cappings are secured at 750 mm intervals, exceeding the 500 mm maximum allowed, causing water bypass via capillary action. Additionally, the upstand turn-up measures 60 mm instead of meeting the 40 mm detailing limit in HB 39 and the NCC.
The flashing upstand measures only 20 mm, which is insufficient to prevent water ingress during driving rain. Roof upstands require greater vertical height to resist overtopping.
Standards
- AS 1562.1 Suggested reference, unverified
- HB 39 Said in videoSuggested reference, unverified
- NCC Said in video
Explained in our own words. Check the current edition; which edition applies depends on the building permit date.
Also relevant to
Video examples
- I Inspected a Billionaire’s Mansion 28:52 majorExcessive roof flashing fixing spacing and non-compliant upstand height
- Off The Plan Disaster Revealed! 13:53 majorUndersized upstand on roof flashing