Parapet and roof capping missing anti-capillary breaks

3 examples in 3 videos 1 major 2 minor

What it is

Parapet cappings provide barely 20 mm lap at corners, lacking sufficient lap depth, and have been cut without required anti-capillary breaks. The distorted sheet metal allows water to track underneath via capillary action directly into wall cavities.

The metal roof capping has been cut flat without an anti-capillary break at the join. The installation excessively relies on smeared surface silicone instead of mechanical water shedding.

The metal parapet capping has been trimmed down, completely removing the required anti-capillary break. This modification compromises weathertightness and facilitates water creep beneath the metalwork.

Standards

Explained in our own words. Check the current edition; which edition applies depends on the building permit date.