Undersized or non-compliant roof sump dimensions
What it is
The hydraulic engineer specified an undersized sump dimension that fails to meet minimum sizing requirements. The specified box gutter and sump measurements do not work and leave installation details ambiguous for the plumber.
The installed roof sump fails to satisfy minimum width criteria, and the overflow arrangement does not comply with high-capacity overflow requirements. Additionally, the gutter joins exceed the maximum allowable spacing, and required movement joints were omitted.
Two box gutters discharge into a sump measuring approximately 200 mm in depth or width. This is non-compliant as the minimum required size is 300 mm.
Standards
- AS/NZS 3500.3 Said in videoSuggested reference, unverified
- HB 114 Said in videoSuggested reference, unverified
Explained in our own words. Check the current edition; which edition applies depends on the building permit date.