Waterproofing wet areas

Bathroom & Wet Area Doorway Threshold Waterstops

8 examples in 7 videos 8 major

What it is

The doorway transition separating the wet area from the dry zone lacks a waterproofed waterstop angle, and no liquid membrane is applied to the concrete substrate beneath the tiles. Unsealed gaps were merely filled with excess silicone.

The threshold angle in the bedroom ensuite is not integrated or terminated with the perimeter waterproofing flashing, breaching AS 3740. Shower enclosures in the adjacent bathrooms similarly lack functional waterstop barriers.

A vertical waterstop was omitted at the junction between the wet area and adjacent door frame where the shower is in close proximity to the opening. Without this barrier, water migrating beneath the tile bed can wick into timber door architraves and cause swelling or decay.

Standards

Explained in our own words. Check the current edition; which edition applies depends on the building permit date.