Defective or missing waterstop angles and threshold drainage
What it is
Inspection along the master ensuite shower sill reveals that the perimeter waterstop angle profile is improperly installed and non-conforming. This fails National Construction Code waterproofing mandates.
No waterstop termination was installed along the door opening, and the external perimeter lacks a strip drainage system. This allows surface runoff to enter directly into internal living areas.
The external balcony tiling sits higher than the internal floor level instead of providing the required downward step-down or membrane termination height. Additionally, no sub-sill strip drainage was installed to prevent water ingress into the dwelling.
Standards
- AS 4654.2 Said in videoSuggested reference, unverified
- NCC Said in video
- NCC Vol 2 Suggested reference, unverified
Explained in our own words. Check the current edition; which edition applies depends on the building permit date.
Also relevant to
Drainage stormwaterStairs balustrades decksWindows doors
Video examples
- I Inspected a Billionaire’s Mansion 15:13 majorNon-compliant shower waterstop angle profile in master ensuite
- I Inspected Troy Candy's Multi-Million Dollar Home: Shocking Finds! 24:48 majorMissing waterstop angle and perimeter strip drain at threshold
- She Paid $20,000 For This Balcony. The Next Was $18,000 Cash 12:30 majorBalcony finished level higher than interior and lacking strip drain